| In DLA mode, partial
discharges are integrated within the bridge,
so integrated charge and energy / cycle can be
measured with loop method as described in ASTM D3382 In PD
mode, partial discharges can be
measured as apparent charge. The
bandpass detector filter is designed in
concordance to the PD frequency characteristics
of windings of rotating machinery.
Portable
high voltage transformer and compensation
reactors are available for field testing of
rotating machinery, power transformers, bushings,
etc.
SPECIFICATIONS
DLA 16:
Voltage
range
0 - 16 kV
Capacity
Ranges: 1 nF - 10 nF - 100 nF - 1 mF; (5 mF
with external standard capacitor)
Resolution: 0.01 % of range
Accuracy: ± 0.2 % of range
Loss
Angle (tg d)
Range: 10 %
Resolution: 0.01 %
Accuracy: ± 0.05 %
Integrated
charge
Sensitivity: 0.2 - 2 - 20 - 200 nC/mV
Coupling
capacitor
Capacity: 10 nF
Voltage: 16 kV max.
PD
Calibrator according to IEC 270
1,000 pC - 10,000 pC
Accessories:
High
Voltage Source including:
Technical
literature and bibliography available upon
request
|